Boiler blowdown, water TDS controller Lakewood Instruments model 1575e. Select add on options from dropdown list

In Stock

$ 1,289.00

Boiler water TDS controller, designed to measure the hot boiler water conductivity (sensor SR2) and open or close a motorized ball valve, that will drain water from the boiler. The automatic control of water TDS allows the boiler to operate at safe levels of water concentration with the minimum amount of energy loses. Read article here for more details.

The sensor works up to 600 psi and 486 Deg F. Orifice plate needed to assure the integrity of the sensor. Below the available kits

    • Part Number 1229239 is just the Model 1575e Controller only
    • Part Number 1229244  is Automated Kit for 1/2" pipes - Includes 1575e Controller, SR2 Sensor, 1/2" Union, Orifice plate.
    • Part Number 1229245 is Automated Kit for 1/2" pipes - Includes 1575e Controller, SR2 Sensor, 1/2" Union, Orifice plate.
    • Part Number 1229243 is for Continuous Sampling - Includes 1575e Controller, SR2 Sensor, PLKT (The PLKT Plumbing Kit Includes 1/2" sample/cycle and continuous sample kit. Unions, Orifice plates, Cross, Tees, and Manual Block Valve Only. Does not include piping.)
MORE INFO

Use code CCFTWZV2NJG3  for an instant 15% discount on checkout!

Lakewood Instruments boiler blowdown, conductivity controller 1575E , including controller, SR2 & PLKT plumbing. just add a motorized ball valve and you are good to go.

PLKT Plumbing kit. 1⁄2” sample/cycle and continuous sample kit
Includes unions, orifice plates, cross, tee, and manual block valve only

The Model 1575e uses the latest in microprocessor capability, giving the user a high level of application flexibility. A large illuminated graphics screen, multiple
inputs, and very easy setup characterize this new technology. The Model 1575e is ETL approved.

    Watch this video to see the 1575e in operation! Click HERE

    FEATURES

    • Removable power cord and receptacles for simple conduit installations.
    • Scheduled feed, which can use three relays for biocides or other chemicals.
    • Two (2) water meter inputs, two (2) drum switch inputs, conductivity input, flow switch input, 4-20 mA output,
    and remote conductivity input via 4-20 mA are all standard features.
    • Designed with a single circuit board for better reliability and lower cost.
    • Large open shallow enclosure for easy wiring.
    • Ball valve delay feature allows accurate control of motorized ball valves.
    • Heavy-duty stainless steel domed numeric keypad and illuminated graphical display allow for quick and easy
    programming. Steel domed switches improve the tactile sensing and life expectancy of the keypad.
    • LED indicators for power, alarm and relay status.

    BENEFITS

    Easy to program with the Lakewood plain English, intuitive, and user friendly menu interface.
    • Controller can be used in boiler, cooling tower, or condensate applications when used with the appropriate
    conductivity sensor.
    • Single circuit board design improves reliability.
    • No add-on options. 4-20 mA output and feed schedule clock features are standard.

    SPECIFICATIONS

    Conductivity range

    500-8000 µS for Boilers

    Conductivity sensor

    2 electrode

    Conductivity Resolution

    ± 10 µS (conductivity <5000 µS)

    Temperature comp.

    ± 100µS (conductivity <5000 µS)

    500NTC, NONE

    Accuracy & repeatability

    ± 1.0%

    Deadband/Setpoint

    Programmable

    Auto/Manual outputs

    Menu selectable

    Keypad

    16 tactile push-buttons

    Display

    illuminated 128x64 pixel LCD

    Drum Switch Inputs

    2 digital contact inputs

    Water meter inputs (2)

    Contact head, paddle

    Timers

    wheel or turbine

    Max. blowdown time exceeded

    Output Signal

    and relay run time exceeded

    One 4 – 20 mA, isolated or

    non-isolated optionally powered

    output for conductivity


    Input Signal

    One 4-20 mA, non- isolated

    internally powered input for

    Output relays

    conductivity

    4, 3 selectable use,

    Relay ratings

    1 blowdown

    3A each, 10A total

    Power

    120/240 VAC 50/60 Hz

    Ambient

    32° - 120°F (0 - 49°C)

    Enclosure

    NEMA 4X, ETL

      

    Sensors/Plumbing

    Boiler

    Max Pressure

    600 psi (41.3 bar)

    Max Temp

    486°F (252°C)