1269226 CONTROLLER KIT 140 w/ 185 &

The Model 140 uses the latest in microprocessor capability, giving the

user a high level of application flexibility. Multiple inputs and very

easy setup characterize this new technology. Water meters, sensors

and plumbing assemblies are purchased separately.

 140 with cooling tower Right Exit flowswitch and sensor p/n 1269226

  • Use this Controller for cooling towers.
  • Removable power cord and receptacles for simple conduit installations.
  • Scheduled feed, which can use two relays for biocides or other chemicals.
  • One (1) water meter input, conductivity input, flow switch input, and 4-20 mA output are all standard features.
  • Designed with a single circuit board for better reliability and lower cost.
  • Large open shallow enclosure for easy wiring.
  • The enclosure is rated NEMA 4X.
  • Power selector switch for 115 or 230 vac operation.
  • Heavy-duty stainless steel domed numeric keypad and illuminated graphical display allow for quick and

easy programming. Steel domed switches improve the tactile sensing and life expectancy of the keypad.

  • LED indicators for power, alarm and relay status.

 

  • Easy to program with the Lakewood plain English, intuitive, and user friendly menu interface.
  • Single circuit board design improves reliability.
  • No add-on options. 4-20 mA output and biocide features are standard.
  • Multiple methods of chemical feed for application flexibility.

 

Conductivity range 0-10,000 μS Output Signal One 4 – 20 mA, isolated or

Conductivity sensor 2 electrode non-isolated optionally

Conductivity Resolution ± 10 μS powered

Temperature comp. 500 ohm NTC Output relays 2 selectable use, 1 blowdown

Accuracy & repeatability ± 1.0% Relay ratings 3A each, 10A total

Deadband/Setpoint Adjustable Power 120/240 VAC 50/60 Hz

Auto/Manual outputs Menu selectable Ambient 32° - 120°F (0 - 49°C)

Keypad 16 tactile push-buttons Enclosure N E M A 4X, ETL

Display 16 X 2 Character

Water meter input Contact head, paddle wheel

or turbine Sensors/Plumbing Cooling Tower

Timer Max. blowdown time exceeded, Max Pressure 140 psi (9.65 bar)@ 100 °F

relay time exceeded Max Temp 140°F (60°C)

Min flow 1 gpm (3.785 Lpm)

 