Lakewood Model 1575e Cooling Tower Controller (Controller only)

Cooling tower options for 1575e controller

Customizations Total: $ 0.00

The Model 1575e is a dedicated cooling tower water treatment controller, which uses the latest in microprocessor capability, giving the user a high level of application flexibility. A large illuminated graphics screen, multiple inputs, and very easy setup characterize this new technology. The Model 1575e is ETL approved.

The base controller is the Lakewood p/n 1229239, please use the options to select the combination required for your specific application.

  • Removable power cord and receptacles for simple conduit installations.
  • Scheduled feed, which can use three relays for biocides or other chemicals.
  • Two (2) water meter inputs, two (2) drum switch inputs, conductivity input, a flow switch input, a 4-20 mA output, and a 4-20 mA input are all standard features.
  • The 4-20 mA input can be used with a transmitter for one of the following: remote conductivity, makeup conductivity, pH, ORP, percent, pressure, milliamps, flow rates, or traced chemistry control. This transmitter can be added in the field.
  • Designed with a single circuit board for better reliability and lower cost.
  • Large open shallow enclosure for easy wiring.
  • Ball valve delay feature allows accurate control of motorized ball valves.
  • Heavy-duty stainless steel domed numeric keypad and illuminated graphical display allow for quick and easy programming. Steel domed switches improve the tactile sensing and life expectancy of the keypad.
  • LED indicators for power, alarm and relay status.

 BENEFITS

  • Easy to program with the Lakewood plain English, intuitive, and user friendly menu interface.
  • Controller can be used in boiler, cooling tower, or condensate applications when used with the appropriate conductivity sensor.
  • Single circuit board design improves reliability.
  • No add-on options. 4-20 mA output and feed schedule clock features are standard.
SPECIFICATIONS

Conductivity range                              50-10,000 μS

Conductivity sensor                            2 electrode

Conductivity Resolution                      ± 10 μS (conductivity <5000 μS)

                                                            ±100 μS(conductivity > 5000 μS)

 Temperature comp.                            500NTC, NONE

Accuracy & repeatability                    ± 1.0%

Deadband/Setpoint                             Programmable

Auto/Manual outputs                           Menu selectable

Keypad 16 tactile push-buttons

Display illuminated                              128x64 pixel LCD

Drum Switch Inputs                            2 digital contact inputs

Water meter inputs (2)                        2 digital contact inputs. Contact head, paddle wheel, or turbine

Timers                                                 Max. blowdown time exceeded and relay run time exceeded

Output Signal                                      One 4 – 20 mA, isolated or non-isolated optionally powered output for conductivity

Input Signal                                         One 4-20 mA, non- isolated internally powered input for conductivity

Output                                                 Four (4) relays. 3 for selectable use, 1 for blowdown.

Relay ratings                                       3A each, 10A total

Power                                                  120/240 VAC 50/60 Hz

Ambient                                               32° - 120°F (0 - 49°C)

Enclosure                                            NEMA 4X, ETL

 

Sensors/Plumbing                            Cooling Tower

Max Pressure                                     140 psi (9.65 bar)@ 100 °F

Max Temp                                           140°F (60°C)

Min flow                                                1 gpm (3.785 Lpm)

 

 